Prime rating at rated rpm (as per ISO8528) |
kVA |
1010HD |
|
---|---|---|---|
Kw |
808 |
||
Genset Model |
|
KG1-1010WS |
|
Frequency |
HZ |
50 |
|
Power factor |
Lagging |
0.8 |
|
Voltage |
V |
415(3Ø ) |
|
Governing class (As per ISO 8528 part-V) |
|
G3 |
|
Noise level |
dBA |
NA |
|
Fuel Consumption* |
At 100% load |
Ltrs/Hr |
199 |
At 75% load |
155 |
||
At 50% load |
112 |
||
Fuel tank capacity |
Ltrs |
990 |
|
Overall dimensions of genset (LxWxH)^ |
mm |
7800x2300x2713 |
|
Dry Weight of genset with canopy (approx..)^ |
kg |
13200 |
|
Wet weight of genset with canopy(approx...)^ |
kg |
14500 |
|
Electrical Battery starting voltage |
Volts-DC |
24 |
Engine Model |
|
DV12ETA G1 |
---|---|---|
Rated output(prime Continuous rating as per ISO 8528-1) |
Kw |
889 |
Hp |
1210 |
|
NO. of cylinder |
Number |
16 |
Cubic capacity 2 |
Ltrs |
31.84 |
Bore x stroke |
Mm |
130x150 |
Rated speed |
RPM |
1500 |
Aspiration |
NA/TC/TA |
TA |
Lube Oil change period |
Hrs |
500 |
Lube oil sump capacity Max |
Ltrs |
130 |
Coolant capacity |
Ltrs |
180 |
Insulation Class |
|
Class H |
---|---|---|
Ingression protections |
|
IP 23 |
Altemator Efficiency (at 100% load) 0.8pf** |
% |
95.1 |
Altemator Efficiency (at 75% load) 0.8pf** |
% |
95.4 |
Permissiable Voltage Dip at full load 0.8 pf lag |
Sec |
?19% |
Time to build up rated voltage at rated RPM |
|
< 1 sec provided engine reach the rated speed |
Short circuit Ratio |
|
0.43 |