Prime rating at rated rpm (as per ISO8528) |
kVA |
1500HD |
|
---|---|---|---|
Kw |
1200 |
||
Genset Model |
|
KG1-1500WS |
|
Frequency |
HZ |
50 |
|
Power factor |
Lagging |
0.8 |
|
Voltage |
V |
415(3Ø ) |
|
Governing class (As per ISO 8528 part-V) |
|
G3 |
|
Noise level |
dBA |
Contact Kriloskar Oil Engines Ltd.for Details |
|
Fuel Consumption* |
At 100% load |
Ltrs/Hr |
310 |
At 75% load |
230 |
||
At 50% load |
157 |
||
Fuel tank capacity |
Ltrs |
880 |
|
Overall dimensions of genset (LxWxH)^ |
mm |
5650+x2300+x2680+ |
|
Dry Weight of genset with canopy (approx..)^ |
kg |
13075+ |
|
Wet weight of genset with canopy(approx...)^ |
kg |
14500 |
|
Electrical Battery starting voltage |
Volts-DC |
24 |
Engine Model |
|
124K4300-E1 |
---|---|---|
Rated output(prime Continuous rating as per ISO 8528-1) |
Kw |
1294 |
Hp |
1760 |
|
NO. of cylinder |
Number |
12 |
Cubic capacity 2 |
Ltrs |
51.73 |
Bore x stroke |
Mm |
170x190 |
Rated speed |
RPM |
1500 |
Aspiration |
NA/TC/TA |
TA |
Lube Oil change period |
Hrs |
500 |
Lube oil sump capacity Max |
Ltrs |
265 |
Coolant capacity |
Ltrs |
210 |
Insulation Class |
|
Class H |
---|---|---|
Ingression protections |
|
IP 23 |
Altemator Efficiency (at 100% load) 0.8pf** |
% |
95.4 |
Altemator Efficiency (at 75% load) 0.8pf** |
% |
95.8 |
Permissiable Voltage Dip at full load 0.8 pf lag |
Sec |
≤20% |
Time to build up rated voltage at rated RPM |
|
< 1 sec provided engine reach the rated speed |
Short circuit Ratio |
|
3 Times rated current for "10 sec" |
Overload Withstand Capacity |
% |
10% overload for one hour once in 12 hours |